At a Glance
Description
Technical data
Configuration
Planning and assembly instructions
- Duct device for the installation in the technical room - No disruptive devices in the swimming pool
- 2 sizes
- Different air routing variants permitting a simple duct routing
- Good indoor climate thanks to constant admixture of outside air (accessories)
- Coordinated air duct system
- Heat recovery by using the heat pump principle
- Energy-saving EC direct current motor
- Control box, fully wired, equipped with all necessary load parts, terminal blocks, fuses, etc.
- Room hygrostat
- Control WPCON B
Analogue control including the following functions
Dehumidification
Automatic defrosting
Heating (accessories)
Ventilation (accessories)
Equipment list
Fan, heat pump unit for energy recovery (equipped with compressor, evaporator, condenser, filter dryer, safety refrigerant R407C), condensate collecting tray, air filter, height-adjustable feet, and switching unit with control
Housing
Stable, corrosion-resistant profile frame construction made of aluminium hollow chamber profiles, powder-coated. The profiles are thermally decoupled by means of integrated plastic webs, so that the heat transfer between the device chambers and the environment can be reduced to a minimum level. Cladding panels equipped with highly insulating Hydrotec foam core.
Supply air fan
equipped with energy-saving, stepless EC direct current motors.
Exhaust filter
Slide-in frame equipped with a Z line filter. Filter cell with pleated filter medium, fully incinerable and metal-free.
Heat pump unit
Heat pump unit equipped with a fully hermetic rotary piston/scroll compressor, evaporator, epoxy resin-coated condenser; bypass flap, condensate pan with drain
Switching unit and regulation
integrated in the device with all modules for all tasks in the fields of control and monitoring.
Room hygrostat
Control EWPCON B
Microprocessor control with the following functions:
- Dehumidification
- Automatic defrosting
- Heating (accessories)
- Ventilation (accessories)
Size | 25 | 50 |
---|---|---|
Nominal air throughput m3/h | 600 | 1200 |
Dehumidification performance 1) kg/h | 2.7 | 5.1 |
Dehumidification performance 1) with 20% outside air (L +26°C/43% RH) kg/h |
3.1 | 5.9 |
Maximum water surface 2) without/with outside air content m² | up to 32/36 | 30 – 50/60 |
Limit of the operation temperature °C | +15 °C up to 32 °C | |
Input power KW | 1.2 | 2.1 |
Voltage V | 230 | 400 |
Type | EWP-25 | EWP-50 |
1) Room temperature/humidity + 30 °C / 60 % RH
2) The exact calculation in accordance with the standard VDI 2089 is required
Device
2 sizes
4 design variants
Alternative equipment
- Connection piece for transition to ISO duct
- Connection piece (special size)
- Connection piece for transition to round duct
Additional equipment
- Set PWW heating register EWP
Accessories
- Set outside air
- Set exhaust air
- Motor shut-off valve (outside air/exhaust air)
- Replacement filter
General planning information
- Determination of the size (according to VDI 2089)
- Determination of the space requirements and of the appropriate installation site
- Check of the size of the insertion opening
- Provision of electrical feed to the device
- Provision of electrical cables from the device to the room hygrostat
- Provision of a condensate line from the device to the sewer
- Determination of the number, length, type and position of the supply air floor slot rails
- Determination of the line routing and dimensions for the supply air duct
- Determination of the number, size and position of the exhaust air grilles
- Determination of the line routing and dimensions for the exhaust air duct
General planning information relating to the accessories
- Determination of the position and size of the outside air or exhaust air opening
- Determination of the line routing and dimensions for the external air or exhaust air duct (provision of a filter box in the external air duct!)
- Provision of an electrical lead to the exhaust air fan
- Provision of an electrical lead to the room hygrostat and/or thermostat
- Provision of a (flow and return) heating connection pipe to the device
- Provision of an electrical lead to the feeder pump